10.11.3
Signals
Table 245:
I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 246:
I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
10.11.4
Settings
Table 247:
I103IEDCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
255
Function type (1-255)
10.12
Function commands user defined for IEC 60870-5-103
I103USRCMD
10.12.1
Functionality
I103USRCMD is a command block in control direction with user defined output signals.
These function blocks include the
FunctionType
parameter for each block in the private
range, and the Information number parameter for each output signal.
Section 10
1MRK 511 287-UUS A
Control
360
Technical manual