Table 334:
TEIGGIO Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the warning
limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the alarm
limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the overflow
limit
ACCTIME
REAL
Integrated elapsed time in seconds
11.9.5
Settings
Table 335:
TEIGGIO Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
0 - 1
-
1
1
Disable/Enable Operation
tWarning
1.00 - 999999.99
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.99
s
0.01
1200.00
Time limit for alarm supervision
11.9.6
Operation principle
The elapsed time integrator (TEIGGIO) provides
•
time integration, accumulating the elapsed time when a given binary signal has been
high.
•
blocking and reset.
•
supervision of limit transgression and overflow.
•
retaining of the integrated value if any warning, alarm or overflow occurs.
Figure
describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.
1MRK 511 287-UUS A
Section 11
Logic
415
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...