![ABB REC650 ANSI Скачать руководство пользователя страница 379](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772379.webp)
power interruption. The
RESET
input has priority if both
SET
and
RESET
are
operated simultaneously.
Configurable logic Q/T
A number of logic blocks and timers, with the capability to propagate timestamp and
quality of the input signals, are available. The function blocks assist the user to adapt the
IEDs configuration to the specific application needs.
•
ORQT
OR function block that also propagates timestamp and quality of input
signals. Each block has six inputs and two outputs where one is inverted.
•
INVERTERQT
function block that inverts the input signal and propagates
timestamp and quality of input signal.
•
PULSETIMERQT
Pulse timer function block can be used, for example, for pulse
extensions or limiting of operation of outputs. The function also propagates
timestamp and quality of input signal.
•
XORQT
XOR function block. The function also propagates timestamp and quality
of input signals. Each block has two outputs where one is inverted.
•
TIMERSETQT
function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay. The function also propagates
timestamp and quality of input signal.
•
ANDQT
AND function block. The function also propagates timestamp and quality
of input signals. Each block has four inputs and two outputs where one is inverted.
•
SRMEMORYQT
function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to the
state before the interruption, or be reset. The function also propagates timestamp and
quality of input signal.
•
RSMEMORYQT
function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to the
state before the interruption, or be reset. The function also propagates timestamp and
quality of input signal.
1MRK 511 287-UUS A
Section 11
Logic
373
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...