![ABB REC650 ANSI Скачать руководство пользователя страница 583](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772583.webp)
The function IEC60870-5-103 serial communication for RS485, RS485103, is used to
configure the communication parameters for the RS485 serial communication interface.
14.9.2
Settings
Table 480:
OPTICAL103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 255
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
RevPolarity
Disabled
Enabled
-
-
Enabled
Invert polarity
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
Disabled
5ms
10ms
20ms
40ms
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
Table 481:
RS485103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 255
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
Disabled
5ms
10ms
20ms
40ms
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
1MRK 511 287-UUS A
Section 14
Station communication
577
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...