12.16.4
Signals
Inputs PRESSURE and TEMP together with settings
PressAlmLimit
,
PressLOLimit
,
TempAlarmLimit
and
TempLOLimit
are not supported in
this release of 650 series.
Table 419:
SSIMG (63) Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLK_ALM
BOOLEAN
0
Block all the alarms
PRESSURE
REAL
0.0
Pressure input from CB
TEMP
REAL
0.0
Temperature of the insulation medium from CB
PRES_ALM
BOOLEAN
0
Pressure alarm signal
PRES_LO
BOOLEAN
0
Pressure lockout signal
SET_P_LO
BOOLEAN
0
Set pressure lockout
SET_T_LO
BOOLEAN
0
Set temperature lockout
RESET_LO
BOOLEAN
0
Reset pressure and temperature lockout
Table 420:
SSIMG (63) Output signals
Name
Type
Description
PRESSURE
REAL
Pressure service value
PRES_ALM
BOOLEAN
Pressure below alarm level
PRES_LO
BOOLEAN
Pressure below lockout level
TEMP
REAL
Temperature of the insulation medium
TEMP_ALM
BOOLEAN
Temperature above alarm level
TEMP_LO
BOOLEAN
Temperature above lockout level
12.16.5
Settings
Table 421:
SSIMG (63) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
PressAlmLimit
0.00 - 25.00
-
0.01
5.00
Alarm setting for pressure
PressLOLimit
0.00 - 25.00
-
0.01
3.00
Pressure lockout setting
TempAlarmLimit
-40.00 - 200.00
-
0.01
30.00
Temperature alarm level setting of the medium
Table continues on next page
Section 12
1MRK 511 287-UUS A
Monitoring
520
Technical manual