12.15.5
Settings
Table 415:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
RtdBattVolt
20.00 - 250.00
V
1.00
110.00
Battery rated voltage
BattVoltLowLim
60 - 140
%Vbat
1
70
Lower limit for the battery terminal voltage
BattVoltHiLim
60 - 140
%Vbat
1
120
Upper limit for the battery terminal voltage
tDelay
0.000 - 60.000
s
0.001
0.200
Delay time for alarm
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset of alarm
12.15.6
Measured values
Table 416:
SPVNZBAT Measured values
Name
Type
Default
Description
V_BATT
REAL
0.00
Battery terminal voltage that has to be supervised
BLOCK
BOOLEAN
0
Blocks all the output signals of the function
12.15.7
Monitored Data
Table 417:
SPVNZBAT Monitored data
Name
Type
Values (Range)
Unit
Description
BATTVOLT
REAL
-
kV
Service value of the battery
terminal voltage
12.15.8
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are
Enable
and
Disable
.
The function execution requires that at least one of the function outputs is
connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
1MRK 511 287-UUS A
Section 12
Monitoring
517
Technical manual
Содержание REC650 ANSI