outputs, where one is inverted. The memory setting controls if the flip-flop after a power
interruption will return the state it had before or if it will be reset.
SRMEMORYQT propagates quality and time as well as value.
Table 305:
Truth table for SRMEMORYQT function block
SET
RESET
OUT
NOUT
0
0
Last
value
Inverted
last value
0
1
0
1
1
0
1
0
1
1
1
0
If
Memory
parameter is
Enabled
, the output result is stored in semi-retained memory.
Function block
SRMEMORYQT
SET
RESET
OUT
NOUT
IEC09000301-1-en.vsd
IEC09000301 V1 EN
Figure 185:
SRMEMORYQT function block
Signals
Table 306:
SRMEMORYQT Input signals
Name
Type
Default
Description
SET
BOOLEAN
0
Input signal to set
RESET
BOOLEAN
0
Input signal to reset
Table 307:
SRMEMORYQT Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Section 11
1MRK 511 287-UUS A
Logic
392
Technical manual