It is important for indication in the SLD that the a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on the
screen. A symbol is created and configured in GDE tool in PCM600.
The PSTO input is connected to the Local remote switch to have a selection of operators
place, operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE
connection from Fixed signal function block (FXDSIGN) will allow operation from local
HMI.
As it can be seen, both indications and commands are done in double-bit representation,
where a combination of signals on both inputs/outputs generate the desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name of
the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1
IPOS2
Name of displayed string Default string value
0
0
PosUndefined
P00
1
0
Position1
P01
0
1
Position2
P10
1
1
PosBadState
P11
10.7
IEC 61850 generic communication I/O functions
DPGGIO
10.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO
-
-
10.7.2
Functionality
The IEC 61850 generic communication I/O functions DPGGIO function block is used to
send double indications to other systems or equipment in the substation using IEC61850.
It is especially used in the interlocking and reservation station-wide logics.
1MRK 511 287-UUS A
Section 10
Control
351