![ABB REC650 ANSI Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772169.webp)
6.12.3
Function block
ANSI09000125-1-en.vsd
DNSPTOC (46)
I3P*
V3P*
BLOCK
BLKOC1
ENMLTOC1
BLKOC2
ENMLTOC2
TRIP
TROC1
TROC2
BFI_3P
PU_OC1
PU_OC2
DIROC1
DIROC2
CURRENT
VOLTAGE
VIANGLE
ANSI09000125 V1 EN
Figure 67:
DNSPTOC (46) function block
6.12.4
Signals
Table 105:
DNSPTOC (46) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKOC1
BOOLEAN
0
Block of over current function OC1
ENMLTOC1
BOOLEAN
0
Enable signal for current multiplier - step1 (OC1)
BLKOC2
BOOLEAN
0
Block of over current function OC2
ENMLTOC2
BOOLEAN
0
Enable signal for current multiplier - step 2 (OC2)
Table 106:
DNSPTOC (46) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TROC1
BOOLEAN
Trip signal from step 1 (OC1)
TROC2
BOOLEAN
Trip signal from step 2 (OC2)
START
BOOLEAN
General pickup signal
STOC1
BOOLEAN
OC1_PICK UP
STOC2
BOOLEAN
OC2_PICK UP
DIROC1
INTEGER
Directional mode of step 1(non-directional, forward,
reverse)
DIROC2
INTEGER
Directional mode of step 2 (non-directional, forward,
reverse)
Table continues on next page
1MRK 511 287-UUS A
Section 6
Current protection
163
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...