![ABB REC650 ANSI Скачать руководство пользователя страница 232](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772232.webp)
Table 168:
SESRSYN (25) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GblBaseSelBus
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Line
SelPhaseBus1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar1
SelPhaseBus2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar2
SelPhaseLine1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line1
SelPhaseLine2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line2
10.1.6
Monitored data
Table 169:
SESRSYN (25) Monitored data
Name
Type
Values (Range)
Unit
Description
VDIFFME
REAL
-
-
Calculated difference of
voltage in p.u of set voltage
base value
FRDIFFME
REAL
-
Hz
Calculated difference of
frequency
PHDIFFME
REAL
-
deg
Calculated difference of phase
angle
Vbus
REAL
-
kV
Bus voltage
VLine
REAL
-
kV
Line voltage
Section 10
1MRK 511 287-UUS A
Control
226
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...