![ABB REC650 ANSI Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772070.webp)
Table 16:
GRP1_LED1 Input signals
Name
Type
Default
Description
HM1L01R
BOOLEAN
0
Red indication of LED1, local HMI alarm group 1
HM1L01Y
BOOLEAN
0
Yellow indication of LED1, local HMI alarm group 1
HM1L01G
BOOLEAN
0
Green indication of LED1, local HMI alarm group 1
Table 17:
LEDGEN Output signals
Name
Type
Description
NEWIND
BOOLEAN
New indication signal if any LED indication input is set
ACK
BOOLEAN
A pulse is provided when the LEDs are acknowledged
5.3.4
Settings
Table 18:
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
tRestart
0.0 - 100.0
s
0.1
0.0
Defines the disturbance length
tMax
0.0 - 100.0
s
0.1
0.0
Maximum time for the definition of a
disturbance
Table 19:
GRP1_LED1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SequenceType
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
-
Follow-S
Sequence type for LED 1, local HMI alarm
group 1
LabelOff
0 - 18
-
1
G1L01_OFF
Label string shown when LED 1, alarm group 1
is off
LabelRed
0 - 18
-
1
G1L01_RED
Label string shown when LED 1, alarm group 1
is red
LabelYellow
0 - 18
-
1
G1L01_YELLOW
Label string shown when LED 1, alarm group 1
is yellow
LabelGreen
0 - 18
-
1
G1L01_GREEN
Label string shown when LED 1, alarm group 1
is green
Section 5
1MRK 511 287-UUS A
Local Human-Machine-Interface LHMI
64
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...