![ABB REC650 ANSI Скачать руководство пользователя страница 534](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772534.webp)
12.18.6
Monitored data
Table 430:
SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
CBOTRVT
REAL
-
ms
Travel time of the CB during
opening operation
CBCLTRVT
REAL
-
ms
Travel time of the CB during
closing operation
SPRCHRT
REAL
-
s
The charging time of the CB
spring
NO_OPR
INTEGER
-
-
Number of CB operation cycle
NOOPRDAY
INTEGER
-
-
The number of days CB has
been inactive
CBLIFE_A
INTEGER
-
-
CB Remaining life phase A
CBLIFE_B
INTEGER
-
-
CB Remaining life phase B
CBLIFE_C
INTEGER
-
-
CB Remaining life phase C
IACC_A
REAL
-
-
Accumulated currents power
(Iyt), phase A
IACC_B
REAL
-
-
Accumulated currents power
(Iyt), phase B
IACC_C
REAL
-
-
Accumulated currents power
(Iyt), phase C
12.18.7
Operation principle
The circuit breaker condition monitoring function includes a number of metering and
monitoring subfunctions. The functions can be enabled and disabled with the
Operation
setting. The corresponding parameter values are Enable and Disable. The operation
counters are cleared when
Operation
is set to
Disabled
.
The operation of the functions can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Section 12
1MRK 511 287-UUS A
Monitoring
528