Table 343:
CMMXU Output signals
Name
Type
Description
I_A
REAL
IA Amplitude
IA_RANGE
INTEGER
Phase A current magnitude range
IA_ANGL
REAL
IA Angle
I_B
REAL
IB Amplitude
IB_RANGE
INTEGER
Phase B current magnitude range
IB_ANGL
REAL
IB Angle
I_C
REAL
IC Amplitude
IC_RANGE
INTEGER
Phase C current magnitude range
IC_ANGL
REAL
IC Angle
12.1.3.4
Settings
Table 344:
CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ILDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
ILMax
0 - 500000
A
1
1300
Maximum value
ILRepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
ILAngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Table 345:
CMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ILZeroDb
0 - 100000
m%
1
500
Zero point clamping
ILHiHiLim
0 - 500000
A
1
1200
High High limit (physical value)
ILHiLim
0 - 500000
A
1
1100
High limit (physical value)
ILLowLim
0 - 500000
A
1
0
Low limit (physical value)
ILLowLowLim
0 - 500000
A
1
0
Low Low limit (physical value)
ILMin
0 - 500000
A
1
0
Minimum value
ILLimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
Table continues on next page
1MRK 511 287-UUS A
Section 12
Monitoring
427
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...