![ABB REC650 ANSI Скачать руководство пользователя страница 601](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772601.webp)
Design of the time system (clock synchronization)
SW-time
Protection
and control
functions
Time tagging and general synchronization
Commu
- nication
Events
ANSI09000210-1-en.vsd
External
synchronization
sources
Disabled
SNTP
DNP
IRIG-B
Time-
regulator
IEC60870-5-103
ANSI09000210 V1 EN
Figure 266:
Design of time system (clock synchronization)
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical structure. A
function is synchronized from a higher level and provides synchronization to lower levels.
Function
Synchronization from
a higher level
Optional synchronization of
modules at a lower level
IEC09000342-1-en.vsd
IEC09000342 V1 EN
Figure 267:
Synchronization principle
A function is said to be synchronized when it periodically receives synchronization
messages from a higher level. As the level decreases, the accuracy of the synchronization
decreases as well. A function can have several potential sources of synchronization, with
different maximum errors. This gives the function the possibility to choose the source with
the best quality, and to adjust its internal clock after this source. The maximum error of a
clock can be defined as:
1MRK 511 287-UUS A
Section 15
Basic IED functions
595
Technical manual