Table 189:
LOCREM Output signals
Name
Type
Description
OFF
BOOLEAN
Control is disabled
LOCAL
BOOLEAN
Local control is activated
REMOTE
BOOLEAN
Remote control is activated
VALID
BOOLEAN
Outputs are valid
10.3.6.5
Settings
Table 190:
LOCREM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ControlMode
Internal LR-switch
External LR-switch
-
-
Internal LR-switch
Control mode for internal/external LR-switch
10.3.7
Local remote control LOCREMCTRL
10.3.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local remote control
LOCREMCTRL
-
-
10.3.7.2
Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
Section 10
1MRK 511 287-UUS A
Control
258
Technical manual