13.2.5
Settings
Table 455:
ETPMMTR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable/Disable
StartAcc
Disabled
Enabled
-
-
Disabled
Activate the accumulation of energy values
tEnergy
1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
-
-
1 Minute
Time interval for energy calculation
tEnergyOnPls
0.000 - 60.000
s
0.001
1.000
Energy accumulated pulse ON time
tEnergyOffPls
0.000 - 60.000
s
0.001
0.500
Energy accumulated pulse OFF time
EAFAccPlsQty
0.001 - 10000.000
MWh
0.001
100.000
Pulse quantity for active forward accumulated
energy value
EARAccPlsQty
0.001 - 10000.000
MWh
0.001
100.000
Pulse quantity for active reverse accumulated
energy value
ERFAccPlsQty
0.001 - 10000.000
MVArh
0.001
100.000
Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty
0.001 - 10000.000
MVArh
0.001
100.000
Pulse quantity for reactive reverse
accumulated energy value
Table 456:
ETPMMTR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
EALim
0.001 -
10000000000.000
MWh
0.001
1000000.000
Active energy limit
ERLim
0.001 -
10000000000.000
MVArh
0.001
1000.000
Reactive energy limit
EnZeroClamp
Disabled
Enabled
-
-
Enabled
Enable of zero point clamping detection
function
LevZeroClampP
0.001 - 10000.000
MW
0.001
10.000
Zero point clamping level at active Power
LevZeroClampQ
0.001 - 10000.000
MVAr
0.001
10.000
Zero point clamping level at reactive Power
DirEnergyAct
Forward
Reverse
-
-
Forward
Direction of active energy flow Forward/
Reverse
DirEnergyReac
Forward
Reverse
-
-
Forward
Direction of reactive energy flow Forward/
Reverse
EAFPrestVal
0.000 - 10000.000
MWh
0.001
0.000
Preset Initial value for forward active energy
EARPrestVal
0.000 - 10000.000
MWh
0.001
0.000
Preset Initial value for reverse active energy
ERFPresetVal
0.000 - 10000.000
MVArh
0.001
0.000
Preset Initial value for forward reactive energy
ERRPresetVal
0.000 - 10000.000
MVArh
0.001
0.000
Preset Initial value for reverse reactive energy
1MRK 511 287-UUS A
Section 13
Metering
557
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...