![ABB REC650 ANSI Скачать руководство пользователя страница 174](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772174.webp)
7.1.4
Signals
Table 111:
UV2PTUV (27) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLK1
BOOLEAN
0
Block of step 1
BLK2
BOOLEAN
0
Block of step 2
Table 112:
UV2PTUV (27) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRST1
BOOLEAN
Trip signal from step 1
TRST2
BOOLEAN
Trip signal from step 2
PICKUP
BOOLEAN
General pickup signal
PU_ST1
BOOLEAN
Start signal from step 1
PU_ST1_A
BOOLEAN
Pick up signal from step 1 phase A
PU_ST1_B
BOOLEAN
Pick up signal from step 1 phase B
PU_ST1_C
BOOLEAN
Pick up signal from step 1 phase C
PU_ST2
BOOLEAN
Start signal from step 2
7.1.5
Settings
Table 113:
UV2PTUV (27) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
OperationStep1
Disabled
Enabled
-
-
Enabled
Enable execution of step 1
Characterist1
Definite time
Inverse curve A
Inverse curve B
-
-
Definite time
Selection of time delay curve type for step 1
OpMode1
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1 of 3, 2
of 3, 3 of 3) from step 1
Pickup1
1 - 100
%VB
1
70
Voltage start value (DT & IDMT) in % of VBase
for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
Table continues on next page
Section 7
1MRK 511 287-UUS A
Voltage protection
168
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...