Function
Range or value
Accuracy
Operate time, directional
30 ms typically at 0 to 2 x I
set
20 ms typically at 0 to 10 x I
set
-
Reset time, directional
40 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
2 ms typically at 0 to 10 x I
set
-
Impulse margin time
15 ms typically
-
Dynamic overreach
< 10% at t = 300 ms
-
Section 6
1MRK 511 287-UUS A
Current protection
166
Technical manual