10.13.3
Signals
Table 251:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
Table 252:
I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
10.13.4
Settings
Table 253:
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
10.14
IED commands with position and select for IEC
60870-5-103 I103POSCMD
10.14.1
Functionality
I103POSCMD has double-point position indicators that are getting the position value as
an integer (for example from the POSITION output of the SCSWI function block) and
sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not define
the use of values 0 and 3 . However, when connected to a switching device, these values
are transmitted.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type of
control)
1MRK 511 287-UUS A
Section 10
Control
363
Technical manual