12.6.5
Technical data
Table 392:
DRPRDRE technical data
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
12.7
Sequential of events
12.7.1
Functionality
Continuous event-logging is useful for monitoring the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The sequential of events logs all binary input signals connected to the Disturbance
recorder function. The list may contain up to 1000 time-tagged events stored in a FIFO-
buffer.
12.7.2
Function block
The Sequential of events has no function block of it’s own.
12.7.3
Signals
12.7.3.1
Input signals
The Sequential of events logs the same binary input signals as configured for the
Disturbance report function.
12.7.4
Operation principle
When a binary signal, connected to the disturbance report function, changes status, the
sequential of events function stores input name, status and time in the sequential of events
in chronological order. The list can contain up to 1000 events from both internal logic
signals and binary input channels. If the list is full, the oldest event is overwritten when a
new event arrives.
Section 12
1MRK 511 287-UUS A
Monitoring
492
Technical manual