![ABB REC650 ANSI Скачать руководство пользователя страница 440](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772440.webp)
12.1.6
Voltage sequence measurement VMSQI
12.1.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage sequence measurement
VMSQI
U1, U2, U0
SYMBOL-TT V1 EN
-
12.1.6.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.
ANSI08000224-1-en.vsd
VMSQI
V3P*
3V0
3V0RANG
3V0ANGL
V1
V1RANG
V1ANGL
V2
V2RANG
V2ANGL
ANSI08000224 V1 EN
Figure 201:
VMSQI function block
12.1.6.3
Signals
Table 357:
VMSQI Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
Table 358:
VMSQI Output signals
Name
Type
Description
3V0
REAL
3U0 Amplitude
3V0RANG
INTEGER
3V0 Magnitude range
3V0ANGL
REAL
3U0 Angle
V1
REAL
U1 Amplitude
Table continues on next page
Section 12
1MRK 511 287-UUS A
Monitoring
434
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...