Signals
Table 300:
TIMERSETQT Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 301:
TIMERSETQT Output signals
Name
Type
Description
ON
BOOLEAN
Output signal, pick-up delayed
OFF
BOOLEAN
Output signal, drop-out delayed
Settings
Table 302:
TIMERSETQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
11.3.2.7
ANDQT function block
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
ANDQT function block
ANDQT
-
-
Functionality
ANDQT function is used to form general combinatory expressions with boolean
variables. ANDQT function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to just
use the required number of inputs and leave the rest un-connected. The output OUT has
a default value 0 initially, which will suppress one cycle pulse if the function has been put
in the wrong execution order.
Section 11
1MRK 511 287-UUS A
Logic
390
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...