Comparator
V<BattVoltLowLim
Comparator
U<BattVoltHiLim
V_BATT
PU_VLOW
PU_VHI
AL_VLOW
AL_VHI
ANSI11000292-1-en.vsd
0-tReset
0
0
0-tDelay
0-tReset
0
0
0-tDelay
ANSI11000292 V1 EN
Figure 227:
Functional module diagram
The battery rated voltage is set with the
RtdBattVolt
setting. The value of the
BattVoltLowLim
and
BattVoltHiLim
settings are given in relative per unit to the
RtdBattVolt
setting.
It is possible to block the function outputs by the
BLOCK
input.
Low level detector
The level detector compares the battery voltage
V_BATT
with the set value of the
BattVoltLowLim
setting. If the value of the
V_BATT
input drops below the set value of the
BattVoltLowLim
setting, the pickup signal
PU_VLOW
is activated.
The measured voltage between the battery terminals
V_BATT
is available through the
Monitored data view.
High level detector
The level detector compares the battery voltage
V_BATT
with the set value of the
BattVoltHiLim
setting. If the value of the
V_BATT
input exceeds the set value of the
BattVoltHiLim
setting, the pickup signal
PU_VHI
is activated.
Time delay
When the operate timer has reached the value set by the
tDelay
setting, the
AL_VLOW
and
AL_VHI
outputs are activated. If the voltage returns to the normal value before the
module operates, the reset timer is activated. If the reset timer reaches the value set by
tReset
, the operate timer resets and the
PU_VLOW
and
AL_VHI
outputs are deactivated.
Section 12
1MRK 511 287-UUS A
Monitoring
518