![ABB REC650 ANSI Скачать руководство пользователя страница 622](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772622.webp)
Task time group 1
(5ms)
Task time group 2
(20ms)
Task time group 1 (5ms)
SMAI instance 3 phase group
SMAI_20_1:1
1
SMAI_20_2:1
2
SMAI_20_3:1
3
SMAI_20_4:1
4
SMAI_20_5:1
5
SMAI_20_6:1
6
SMAI_20_7:1
7
SMAI_20_8:1
8
SMAI_20_9:1
9
SMAI_20_10:1
10
SMAI_20_11:1
11
SMAI_20_12:1
12
Task time group 2 (20ms)
SMAI instance 3 phase group
SMAI_20_1:2
1
SMAI_20_2:2
2
SMAI_20_3:2
3
SMAI_20_4:2
4
SMAI_20_5:2
5
SMAI_20_6:2
6
SMAI_20_7:2
7
SMAI_20_8:2
8
SMAI_20_9:2
9
SMAI_20_10:2
10
SMAI_20_11:2
11
SMAI_20_12:2
12
DFTRefGrp7
ANSI11000284-1-en.vsd
SMAI_20_1
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI_20_1
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI11000284 V1 EN
Figure 274:
Configuration for using an instance in task time group 1 as DFT reference
Assume instance SMAI_20_7:1 in task time group 1 has been selected in the
configuration to control the frequency tracking (For the SMAI_20_x task time groups).
Note that the selected reference instance must be a voltage type.
For task time group 1 this gives the following settings:
For SMAI_20_1:1
DFTRefExtOut
set to
DFTRefGrp7
so as to route SMAI_20_7:1 reference to the
SPFCOUT
output,
DFTReference
set to
DFTRefGrp7
so that SMAI_20_7:1 is used as
reference.
For SMAI_20_2:1 to SMAI_20_12:1
DFTReference
set to
DFTRefGrp7
so that SMAI_20_7:1 is used as reference.
For task time group 2 this gives the following settings:
Section 15
1MRK 511 287-UUS A
Basic IED functions
616
Technical manual