![ABB REC650 ANSI Скачать руководство пользователя страница 315](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772315.webp)
Name
Type
Default
Description
989_OP
BOOLEAN
0
989 is in open position
989_CL
BOOLEAN
0
989 is in closed position
989G_OP
BOOLEAN
0
989G is in open position
989G_CL
BOOLEAN
0
989G is in closed position
C152_OP
BOOLEAN
0
152 in module BH_CONN is in open position
C152_CL
BOOLEAN
0
152 in module BH_CONN is in closed position
C6189_OP
BOOLEAN
0
6189 in module BH_CONN is in open position
C6189_CL
BOOLEAN
0
6189 in module BH_CONN is in closed position
C189G_OP
BOOLEAN
0
189G in module BH_CONN is in open position
C189G_CL
BOOLEAN
0
189G in module BH_CONN is in closed position
C289G_OP
BOOLEAN
0
289G in module BH_CONN is in open position
C289G_CL
BOOLEAN
0
289G in module BH_CONN is in closed position
1189G_OP
BOOLEAN
0
Grounding switch 1189G on busbar WA1 is in open
position
1189G_CL
BOOLEAN
0
Grounding switch 1189G on busbar WA1 is in closed
position
VOLT_OFF
BOOLEAN
0
There is no voltage on line and not VT (fuse) failure
VOLT_ON
BOOLEAN
0
There is voltage on the line or there is a VT (fuse) failure
EXDU_89G
BOOLEAN
0
No transmission error from bay containing grounding
switch QC11
689_EX1
BOOLEAN
0
External condition for disconnector 689
689_EX2
BOOLEAN
0
External condition for disconnector 689
189_EX1
BOOLEAN
0
External condition for apparatus 189
189_EX2
BOOLEAN
0
External condition for apparatus 189
989_EX1
BOOLEAN
0
External condition for apparatus 989
989_EX2
BOOLEAN
0
External condition for apparatus 989
989_EX3
BOOLEAN
0
External condition for apparatus 989
989_EX4
BOOLEAN
0
External condition for apparatus 989
989_EX5
BOOLEAN
0
External condition for apparatus 989
989_EX6
BOOLEAN
0
External condition for apparatus 989
989_EX7
BOOLEAN
0
External condition for apparatus 989
Table 211:
BH_LINE_B (3) Input signals
Name
Type
Default
Description
152_OP
BOOLEAN
0
152 is in open position
152_CL
BOOLEAN
0
152 is in closed position
689_OP
BOOLEAN
0
689 is in open position
Table continues on next page
1MRK 511 287-UUS A
Section 10
Control
309
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...