![ABB REC650 ANSI Скачать руководство пользователя страница 456](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772456.webp)
Function
Range or value
Accuracy
Reactive power, Q
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
± 1.0% of S
n
at S ≤ S
n
± 1.0% of S at S > S
n
Apparent power, S
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
± 1.0% of S
n
at S ≤ S
n
± 1.0% of S at S > S
n
Apparent power, S Three phase
settings
cos phi = 1
± 0.5% of S at S > S
n
± 0.5% of S
n
at S ≤ S
n
Power factor, cos (φ)
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
< 0.02
12.2
Event Counter CNTGGIO
12.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
12.2.2
Functionality
Event counter CNTGGIO has six counters which are used for storing the number of times
each counter input has been activated.
12.2.3
Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6
IEC09000090_1_en.vsd
IEC09000090 V1 EN
Figure 209:
CNTGGIO function block
Section 12
1MRK 511 287-UUS A
Monitoring
450
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...