CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
99
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Sets the gain of the analog output AO1.
For P252=1.000 the value of output AO1 is set according to the
description in Figure 6.15.
P252
0.000 to 9.999
AO1 Analog Output
[ 1.000 ]
gain
-
Check the possible options in Table 6.24 and Figure 6.15.
For the values shown in Table 6.24, P253=2, P254=1000 and
AO2=20mA.
P253
0 to 10
AO2 Analog Ouput
[ 0=Not Used ]
Function
-
(0 to 20)mA or
(4 to 20)mA
Sets the gain of the analog output AO2.
For P254=1.000 the value of output AO2 é is set according to the
description in Figure 6.15.
P254
0.000 to 9.999
AO2 Analog Output
[ 1.000 ]
Gain
0.001
It selects the signal type of the current analog output AO2.
P255
0 or 1
AO2 Analog Output
[ 0=0-20mA ]
Type (0 to 20)mA or
-
(4 to 20)mA
P255
Output type
0
(0 to 20)mA
1
(4 to 20)mA
For transforming the current analog output AO2 to a voltage output of
0 to 10V, connect a resistor of 500
± 1% 0.5W in parallel with the
output signal a resistor of 500
± 1% 0.5W.
Remember when the output type is selected to 4 to 20mA, this will be
the total range of the signal output.
0% of the signal = 4mA and 100% of the signal = 20mA.
Table 6.23
- AO2 signal type
Check possible options in table 6.24 and Figure 6.15.
For the values shown in Table 6.24, P252=1000 and AO1=10V.
P251
0 to 10
AO1 Output Function
[ 0=Not used ]
(0 to 10)V
-
Figure 6.14
- Motor direction of rotation with “Jog only”
U(V)
0
P511
P102
P102
P511
t(s)
“JOG Only”
This option allows the slow speed with Jog in both forward and reverse
directions without auxiliary contactors connected at the input power
supply.
See more information and the notes at the P510 and P511 parameters.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]