CHAPTER 3 - INSTALLATION AND CONNECTION
27
Model
Height
Width
Depth.
A
B
C
D2
Mounting
Weight
Degree of
H
W
D
mm
mm
mm
mm
s c re w
Kg
Protection
mm
mm
mm
(in)
(in)
(in)
(in)
mm
(lb)
(in)
(in)
(in)
(in)
SSW-06.0085
370
132
244
75
350
28.5
8.5
M5
8.5
IP00
SSW-06.0130
(14.57)
(5.20)
(9.61)
(2.95)
(13.78)
(1.12)
(0.33)
(1/4")
(18.74)
SSW-06.0170
440
223
278
150
425
36.5
5.9
M6
18.5
SSW-06.0205
(17.32)
(8.78)
(10.94)
(5.91)
(16.73)
(1.44)
(0.23)
(1/4")
(40.79)
SSW-06.0255
550
370
311
200
527.5
84.8
10
M6
39.5
SSW-06.0312
(21.65)
(14.57)
(12.24)
(7.87)
(20.77)
(3.34)
(0.39)
(1/4")
(87.08)
SSW-06.0365
SSW06.0412
650
369.5
347
200
627.5
84.75
11.25
M6
55.0
SSW06.0480
(25.59)
(14.55)
(13.67)
(7.87)
(24.7)
(3.33)
(0.44)
(1/4")
(121.27)
SSW06.0604
SSW06.0670
795
540
357.12
250
775
145
10
M8
120.0
SSW06.0820
(31.3)
(21.26)
(14.06)
(9.84)
(30.51)
(5.71)
(0.39)
(5/16")
(264.60)
SSW06.0950
894.5
568.2
345.15
400
810
84.1
10
M8
107.0
(35.22)
(22.37)
(13.59)
(15.75)
(31.89)
(3.31)
(0.39)
(5/16")
(235.93)
SSW06.1100
1234.8
685
432.94
500
1110
92.5
15
M8
217.5
SSW06.1400
(48.61)
(26.97)
(17.04)
(19.68)
(43.7)
(3.64)
(0.59)
(5/16")
(479.59)
Table 3.1
- Installation Data with dimensions in mm (in)
At least the spaces around the soft-starter must be left open for the
installation of the SSW-06 Soft-Starter, according to Figure 3.2, as
follows. The dimensions of each space are described in table 3.2.
Install the Soft-Starter SSW-06 in the vertical position according to the
following recommendations:
1) Install the SSW-06 Soft-Starter on a flat surface;
2) Do not place heat sensitive components on top of the SSW-06 Soft-
Starter;
ATTENTION!
If the Soft-Starters are installed one next to the other, use minimum
distance B.
When a Soft-Starter is installed on top of another, use minimum distance
A+C and avoid to the Soft-Starter above the hot air that comes from the
Soft-Starter below.
ATTENTION!
Foresee independent conduits or electroducts for physically separating
the signal, control and power conductors (see item 3.2, electrical
installation).
3.1.3 Positioning / Fixing