SSW-06 - QUICK PARAMETER REFERENCE
16
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting
Setting
Notes presented on quick parameter description:
(1)
This parameter can only be changed with the motor stopped.
(2)
This parameter does not change when factory defaults are loaded (P204=5).
P605
(1)
Phase Voltage Imbalance Time
0=Inactive
1
s
114
1 to 99
Current Protection
P610
(1)
Immediate Undercurrent
0 to 99
20
%
114
(% In of the motor)
P611
(1)
Immediate Undercurrent Time
0=Inactive
0=Inactive
s
114
1 to 99
P612
(1)
Immediate Overcurrent
0 to 99
20
%
114
(% In of the motor)
P613
(1)
Immediate Overcurrent Time
0=Inactive
0=Inactive
s
114
1 to 99
P614
(1)
Current Imbalance between Phases
0 to 30
15
%
115
(% In of the motor)
P615
(1)
Current Imbalance Between
0=Inactive
1
s
115
Phase Times
1 to 99
P616
(1)
Undercurrent before Closing
0=Inactive
1=Active
-
115
of Internal By-pass
1=Active
P617
Motor Overcurrent before By-pass
0=Inactive
1=Active
-
115
1=Active
Phase Sequence
P620
(1)
RST Phase Current Sequence
0=Inactive
0=Inactive
-
115
1=Active
Interval between Starts
P630
Interval of Time after Stop
2 to 999
2
s
115
Motor Thermal Protection
P640
(1)
Motor Protection Thermal Class
0=Inactive
5=25
6=30
-
117
of Motor Protection
1=5
6=30
2=10
7=35
3=15
8=40
4=20
9=45
P641
(1)
Auto-Reset of thermal Memory
0=Inactive
0=Inactive
s
120
1 to 600