CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
97
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The Keypad (HMI) can not be operated while it is executing the read
or write procedures.
NOTES!
1) If the Keypad (HMI) has saved parameters of a “different version”
than that installed in Soft-Starter SSW-06 to which it is trying
to copy the parameters, the operation will not be executed and
Soft-Starter SSW-06 will display error E10 (Error: Copy Function
not permitted). “Different Version” are those that are different in
“x” or “y”, supposing that the numbering of Software Versions is
described as
Vx.yz
.
2) This function changes all SSW-06 parameters to the new values.
It allows the adjustment of the LCD Display contrast, as a function of
the viewing angle. Increase/decrease the parameter content untill the
best contrast is obtained.
P218
0 to 150
LCD Display
[ 127 ]
Contrast Adjustment
-
Defines the command source that will select between the LOCAL /
REMOTE selection condition.
P220
(1)
0 to 8
LOCAL/REMOTE
[ 2 ]
Source Selection
-
P220
Local/Remote Selection
Default Condition
0
Always Local Condition
-
1
Always Remote Condition
-
2
Key
of the Keypad (HMI)
Local
3
Key
of the Keypad (HMI)
Remote
4
Digital Inputs DI4 ... DI6
(P266 ... P268)
5
Serial Communication
Local
6
Serial Communication
Remote
7
Fieldbus Communication
Local
8
Fieldbus Communication
Remote
Default condition = when Soft-Starter SSW-06 is powered-up (start-up)
In the factory default setting, the key
of the Keypad (HMI) will
select Local or Remote Mode. When powered up, the Soft-Starter
SSW-06 starts in Local mode.
Defines the origin of the Soft-Starter SSW-06 enable/disable commands.
P229
(1)
0 to 3
Command Selection
[ 0=HMI ]
-Local Condition
-
P230
(1)
0 to 3
Command Selection
[ 0=Terminals ]
-Remote Condition
-
P229/P230
0
1
2
3
Origin of the Commands
Keypad keys (HMI)
Digital Input DIx
Serial Communication
Fieldbus Communication (DevideNet or Profibus DP)
Table 6.20
- LOCAL/REMOTE Selection
Table 6.21
- Command Selection