CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
83
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P102
1 to 999
Acceleration
[ 20 ]
Ramp Time
1s
When the Soft-Starter SSW-06 has been programmed to Voltage
Ramp Control or Pump Control, this will be the ramp time of the
voltage increment as shown in Figure 6.2.
Figure 6.2 –
Acceleration ramp by Voltage Ramp
When the Soft-Starter SSW-06 has been programmed to Current
Limit control, Torque Control or Current Ramp, this time acts as
maximum starting time, as a protection against locked rotor.
NOTE!
When another control type is selected, not the Voltage Ramp
or Pump Control, the initial voltage will be attenuated due to the
limit imposed by the current.
Figure 6.3 –
Acceleration Ramp by Current Limit
NOTE!
The time set at P102 is not the exact motor acceleration time,
but the voltage ramp time or the maximum start time. The motor
acceleration time will depend on the motor and the load
characteristics.
Start
P102
0
P101
U(V)
100%Un
t(s)
Disable
Enable
Voltage Ramp
Start
P102
0
P110
I(A)
I Limit
t(s)
Disable
Enable
Current Limit
Rated Current
Maximum time