CHAPTER 10 - TECHNICAL SPECIFICATIONS
153
10.3
POWER DATA
Supply
Capacity
Thyristors (SCRs)
Power voltage AC input (R/1L1, S/3L2, T/5L3)
Frequency
Maximum number of starts per hour
Starting Cycle
220V to 575 Vac: (-15% to +10%), or (187 to 632) Vac
50 to 60Hz (± 10 %), or (45 to 66) Hz
10 (1 every 6 minutes) Models 85A to 820A.
5 (1 every 12 minutes) Models 950A to 1400A.
3 x In during 30 s
Maximum reverse peak voltage 1600V
III (UL 508/EN 61010)
Overvoltage Category
NOTE!
Maximum ratings indicated on the tables 10.2 and 10.4 are based on
3 x SSW-06 Soft-Starter Rated Current during 25s and 10 starters per
hour (3xInSSW@ 25s).
10.4 ELECTRONICS/PROGRAMMING DATA
110 to 230 Vac (-15% to +10%), or (94 to 253)Vac
50 to 60Hz (± 10 %), or (45 to 66)Hz
280mA Maximum
Voltage Ramp;
Current Limit;
Pump Control;
Torque Control;
Torque Control;
5 isolated digital inputs;
Minimum high level: 18Vdc;
Maximum low level: 3Vdc;
Maximum Voltage: 30Vdc;
Input Current: 11mA @ 24Vdc;
Programmable functions.
1 input for motor thermistor;
Actuation: 3k9
Release: 1k6
;
Minimum resistance: 100
;
PTCB referenced to the DGND through 249
resistor.
1 analog output, not isolated, (0 to +10)V, RL
10k
(maximum load);
Resolution: 11bits;
Programmable functions.
1 analog output, not isolated,(0 to 20)mA/(4 to 20)mA, RL=500
/1%@10V;
Resolution: 11bits;
Programmable functions.
2 relays with NO-contacts, 240Vac, 1A, programmable functions.
1 relay with NO/NC-contact, 240Vac, 1A, programmable functions.