![WEG SSW-06.0085 User Manual Download Page 35](http://html.mh-extra.com/html/weg/ssw-06-0085/ssw-06-0085_user-manual_950611035.webp)
CHAPTER 3 - INSTALLATION AND CONNECTION
35
f) Models: 1100A and 1400A
* Dimensions in mm (in)
50
(1.97)
89
(3.50)
6
0
.3
(2
.3
7
)
5
8
(2
.2
8
)
104.5
(4.11)
163
(6.42)
100
(3.94)
Output Bus Bar
Power
262
(10.31)
129.4
(5.09)
40
(1.57)
158
(6.22)
40
(1.57)
120
(4.72)
158
(6.22)
40.7
(1.57)
Input Bus Bar
Power
4
0
(1
.5
7
)
2
0
(0
.7
9
)
Stell M12 (12x)
50
(1.97)
Stell M12 (12x)
163
(6.42)
50
(1.97)
4
0
(1
.5
7
)
2
0
(0
.7
9
)
Figura 3.8 f)
– Power terminals
Table 3.5
- Maximum tightening Torque for power connection
Bolt
M6
(1/4")
M8
(5/16")
M10
(3/8")
M10
M12
M12
M12
SSW-06
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.0255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
SSW-06.1100
SSW-06.1400
Torque
Nm (lb.in)
8.3
(74.38)
19
(166.25)
37
(328.12)
37
61
61
61
Bolt
M6
(1/4")
M6
(1/4")
M10
(3/8")
M10
M10
M10
M10
Torque
Nm (lb.in)
8.3
(74.38)
8.3
(74.38)
37
(328.12)
37
37
37
37
Line / Motor
Grounding