CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
84
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P104
1 to 299
Deceleration
[ 0=Inactive ]
Ramp Time
1s
Used in hydraulic pump applications.
Enables and sets the time of the voltage decrement ramp.
For more details about programming and use, refer to Pump Control.
It can be used as Voltage Ramp control, Pump Control, Current Limit
and Current Ramp.
NOTE!
This function is used to lengthen the normal deceleration time of
a load and not to force a shorter time than that imposed by the
load.
P105
30 to 55
End Deceleration
[ 30 ]
Voltage
-
Used in hydraulic pump applications.
Sets the rated voltage (%Un), which will be applied to the motor at
the end of the deceleration ramp.
For more details about the programming and use, refer to Pump
Control.
P103
99 to 60
Voltage Step
[ 100=Inactive ]
during Deceleration
1% Un of the Motor
Used in applications with hydraulic pumps.
Set the rated voltage (%Un), which will be applied to the motor
instantaneously when the Soft-Starter SSW-06 receives the ramp
deceleration command.
For more details about programming and use, refer to Pump Control
at P202.
NOTE!
To enable this function, you must set a deceleration ramp time.
Figure 6.4 –
Deceleration Ramp by voltage decrement
100%Un
P104
0
U(V)
Stop
t(s)
Disable Voltage Ramp
P103
P105
P110
150 to 500
Current Limit
[ 300% ]
1% In of the Motor
Defines the current limit during the motor start as a percentage of
the rated motor current set at P401.
When the current limit is reached during the motor start, the
Soft-Starter SSW-06 will maintain the current at this limit until the
motor reaches the end of the start.
When the current limit is not reached, the motor will start immediately.
For more information about selection of the Current Limit control,
refer to P202.