CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
113
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The under and overvoltage are setting as percentage of the motor
rated voltage (P400).
P600 sets the minimum voltage level at which the motor can operate
without problems. This protection function acts when the line voltage
drops to a value lower than the set and is present during a time equal
to or longer than those set at P601. If this condition is present, the
Soft-Starter is disabled and an Undervoltage Error is displayed.
P602 sets the maximum overvoltage level that the motor allows, during
the time that has been set at P603. If this time is exceeded, the
Soft-Starter is disabled and an Overvoltage Error is displayed.
NOTE!
These functions are active the entire time the motor is running.
P600
(1)
0 to 30
Intermediate
[ 20 ]
Undervoltage
1 %Un of the Motor
P601
(1)
1 to 99
Time of Immediate
[ 1 ]
Undervoltage
1s
P602
(1)
0 to 20
Intermediate
[ 15 ]
Overvoltage
1 %Un of the Motor
P603
(1)
1 to 99
Time of Immediate
[ 1 ]
Overvoltage
1s
6.7 PROTECTIONS PARAMETERS - P600 to P699
Figure 6.22 -
Actuation Levels of the Starting Torque Pulse.
Start
I(A)
I Limit
t(s)
P102
Disable
Enable
Current Ramp
0
P110
P523
P521
I Rated Current
Maximum Time
P112
P111
U(V)
Nominal
t(s)
Disable
Enable
0
P600
P602
Deceleration
ramp
Running
Actuation Region
U(V)
P602
P600
t0
P601
t1(s) t0
P603
t1(s)
Under
Voltage
Nominal
Fault
Action
Nominal
Over
Voltage
Fault
Action
Figura 6.23 -
Actuation Levels in case of Undervoltage and Overvoltage
U (V)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]