CHAPTER 3 - INSTALLATION AND CONNECTION
45
3.2.8 Signal and Control
Connections
The signal connections (analog outputs) and control (relay inputs and
outputs) are made on the electronic card connectors.
Conectors:
CCS6 and CPS63 to the models 85A to 365A and 950A to 1400A.
CCS6 and CPS64 to the models 412A to 820A.
NOTE!
The fans are switched on if the heatsink temperature is above 70ºC
(158ºF). Do not forget to connect the fan power supply and select the
fan supply voltage for the models higher than 255A.
Conector X1A
Description
Specifications
1
Phase
2
Neutral
PE
Ground
Eletronic Supply
(110 to 230)Vac (-15% to +10%) or
(94 to 253)Vac
Operation Current: 280nA Max.
Connector X1B
Factory Standard Function
Specifications
3
DI1
Motor Enable/Disable
4
DI2
Error Reset
5
DI3
Not Used
6
DI4
Not Used
7
DI5
Not Used
5 isolated digital inputs
Minimum high level: 18Vdc
Maximum low level: 3Vdc
Maximum voltage: 30Vdc
Input current: 11mA@24Vdc
8
COM
Common point of the Digital Inputs
9
COM
Common point of the Digital Inputs
10
DGND
0V reference of the 24Vdc source
11
24Vcc
Digital Input Supply
Only use for Digital Inputs
12
PTCB
13
PTCA
DI6 - Not Used
Operation: 3k9
Release: 1k6
Minimum resistance: 110
PTCB referenced to DGND
Through 249
resistor
14
AGND
15
AO1
Input for motor Thermistor
(0 to 10)V, RL 10k (maximum load)
Resolution: 11 bits
16
AGND
17
AO2
Analog Output 1 - Not used
(0 to 20)mA or (4 to 20)mA
RL=500
/1%@10V
Resolution: 11 bits
Conector X1C
Factory Standard Function
Specifications
18
RL1 NA
19
RL1 NA
Relay Output - Run
20
RL2 NA
21
RL2 NA
Relay Output - Full Voltage
22
RL3 NA
23
RL3 C
24
RL3 NF
Relay Output – No Error
Contactor capacity:
1A
24Vac
Conector X1D
Description
Specifications
25
TERM.
26
TERM.
Over-temperature thermostat
27
TC 1/R VER
28
TC 1/R PRET
Current transformer phase R
29
TC 2/S VER
30
TC 2/S PRET
Current transformer phase S
31
TC 3/T VER
32
TC 3/T PRET
Current transformer phase T
Internal connection of the Soft-Starter
Connector X1E
Descrição
Specifications
33
Phase
34
Neutral
Fan Supply (from model 255A)
(101 to 127)Vac or (207 to 253)Vac
Operation current: see table 3.4
P
T
C
Nota:
NC = Normally Closed Contact
NO = Normally Open Contact