CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
85
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Figure 6.5 –
Fixed starting Current Limit
P111
150 to 500
Initial Current by
[ 150 ]
Current Ramp
1% Un of the Motor
Used for the control by Current Ramp, P202=4.
Allows a current limit ramp to be programmed to help in the starting
of loads that have a lower or higher starting torque.
The initial value of the current limit is shown by P111, the final value
is shown by P110 and the time is shown by P112, according to figure
6.6.
P112
1 to 99
Time for Current
[ 20 ]
Ramp
1% of P102
Used for the control by Current Ramp, P202=4.
It enables programming the time, in percent of P102, for the end
Current Ramp.
After the time, programmed at P112, has elapsed, it starts operation
by Current Limit, given by P110.
Start
P102
0
P110
I(A)
t(s)
Disable
Enable
Current Limit
I Limit
Rated Current
Maximum Time
a)
Start
P102
0
P110
I(A)
t(s)
Disable
Enable
Current Limit
I Limit
Rated Current
P111
P112
Maximum Time