CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
106
Range
[Factory Setting]
Parameter
Unit
Description / Notes
6.5 MOTOR PARAMETERS - P400 to P499
Set this parameter value according to the motor nameplate and the
connection diagram in the terminal box.
The motor protection is based on the content of this parameter.
P400
(1)
0 to 999
Motor Rated Voltage
[ 380 ]
1V
Set this parameter value according to the motor nameplate.
The motor protection against current and the current limit are based
on this parameter content.
NOTES!
1) To ensure that these protections operate correctly, the motor
rated current must not be lower than 30% of the rated current
of the Soft-Starter SSW-06.
2) The use of motors that operate with load duties lower than
50% their rated loads are not recommended.
3) Program the rated current of the motor according to the power
supply voltage.
P401
(1)
0.0 to 1500
Motor Rated Current
[ 20.0 ]
0.1A
Set the motor speed according to the motor nameplate data.
The motor speed must be the same as indicated on the motor
nameplate, already considering its slip.
P402
(1)
Motor Rated
Speed
400 to 3600
[ 1780 ]
1 rpm
Set the motor power according to the motor nameplate data.
If the power is in CV or HP, multiply the value by 0,74kW.
P404
(1)
Motor Rated
Power
0.1 to 2650
[ 75 ]
0.1kW
Set the Motor Power Factor according to the motor nameplate data.
P405
(1)
Motor Power
Factor
0 to 1.00
[ 0.89 ]
0.01
Set the Service Factor according to the motor nameplate.
The current protections are based on the content of this parameter.
P406
(1)
0 to 1.50
Service Factor
[ 1.00 ]
0.01