CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
104
Defines the Soft-Starter SSW-06 address on the serial Modbus-RTU
communication network.
For more information, refer to the Serial Communication Manual for
the Soft-Starter SSW-06.
P308
(1)(2)
1 to 247
Soft-Starter address
[ 1 ]
on the Serial
1
Communication
Network
6.4 - SERIAL COMMUNICATION PARAMETERS – P300 to P399
P309
Action
0
Inactive
1
Profibus-DP (1 Input and 1 Output)
2
Profibus-DP (4 Inputs and 4 Outputs)
3
Profibus-DP (7 Inputs and 7 Outputs)
4
DeviceNet (1 Input and 1 Output)
5
DeviceNet (4 Inputs and 4 Outputs)
6
DeviceNet (7 Inputs and 7 Outputs)
P309
(1)(2)
0 to 6
Fieldbus
[ 0=Inactive ]
Communication
-
Board Enabling
Table 6.29
- Fieldbus Communication Protocol Type
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Enables and defines the protocol type of the Fieldbus Communication
Board.
For more information, refer to the Fieldbus Communication Manual for
the Soft-Starter SSW-06.
NOTE!
Without a Fieldbus Communication Board, this parameter must
remain at 0 (not used).
Defines the protocol standards of the serial Modbus-RTU
communication protocol.
For more information, refer to Serial Communication Manual for the
Soft-Starter SSW-06.
P312
(1)(2)
1 to 9
Protocol Type and
[ 1=Modbus-RTU
Transfer Rate of
(9600bps, no
the Serial
parity) ]
Communication.
-
P312
Action
1
Modbus-RTU (9600bps, no parity)
2
Modbus-RTU (9600bps, odd parity)
3
Modbus-RTU (9600bps, even parity)
4
Modbus-RTU (19200bps, no parity)
5
Modbus-RTU (19200bps, odd parity)
6
Modbus-RTU (19200bps, even parity)
7
Modbus-RTU (38400bps, no parity)
8
Modbus-RTU (38400bps, odd parity)
9
Modbus-RTU (38400bps, even parity)
Table 6.30
- Serial Communication Protocol Type
P313
0 to 3
Serial and Fieldbus
[ 0=Off ]
Communication Error
-
Actions
(E28, E29 and E30)
P313
Action
0
Off
1
Disable
2
General Disable
3
Changes to Local
Table 6.31 -
Error action of the Serials and Fieldbus Communication