![WEG SSW-06.0085 User Manual Download Page 150](http://html.mh-extra.com/html/weg/ssw-06-0085/ssw-06-0085_user-manual_950611150.webp)
151
CHAPTER
10
TECHNICAL SPECIFICATIONS
This Chapter describes the technical specifications (electrical and
mechanical) of the Soft-Starters SSW-06.
10.1
CURRENTS AND RATINGS ACCORDING TO UL508
Table 10.1
- Powers and currents for standard connection with three cables according to UL508 (Room temperature of 55ºC)
SSW-06 Model
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
(1)
SSW-06.1100
(1)
SSW-06.1400
(1)
Rated
Current
3xIn @ 30s
A
85
130
170
205
255
312
365
412
480
604
670
820
950
1100
1400
Rated
Current
4.5xIn @ 30s
A
57
87
113
137
170
208
243
275
320
403
447
547
633
733
933
220/230V
hp
kW
30
22
50
37
60
45
75
55
100
75
125
90
150
110
150
112
200
150
250
185
250
185
300
225
350
260
450
330
500
370
380/400V
hp
kW
50
37
75
55
100
75
100
75
150
110
175
130
200
150
250
185
300
225
350
260
400
300
500
370
600
450
700
525
900
670
440/460V
hp
kW
60
45
100
75
125
90
150
110
200
150
250
185
300
220
350
260
400
300
500
370
550
410
600
450
700
525
800
600
1050
775
575V
hp
kW
75
55
125
90
150
110
200
150
250
185
300
220
350
260
450
330
500
370
600
450
650
485
750
550
850
630
1000
750
1350
1000
55ºC
55ºC
SSW-06 Model
SSW-06.0085
SSW-06.0130
SSW-06.0170
SSW-06.0205
SSW-06.0255
SSW-06.0312
SSW-06.0365
SSW-06.0412
SSW-06.0480
SSW-06.0604
SSW-06.0670
SSW-06.0820
SSW-06.0950
(1)
SSW-06.1100
(1)
SSW-06.1400
(1)
Rated
Current
3xIn @ 25s
A
147
225
294
355
441
540
631
713
831
1046
1160
1420
1645
1905
2424
Rated
Current
4.5xIn @ 25s
A
98
150
196
236
294
360
421
475
554
697
773
947
1096
1270
1616
220/230V
hp
kW
50
37
75
55
100
75
125
90
150
110
200
150
250
185
250
185
350
260
450
330
450
330
550
410
650
485
800
600
1000
750
380/400V
hp
kW
75
55
125
90
150
110
200
150
250
185
300
220
350
260
450
330
550
410
700
525
850
630
1000
750
1150
820
1350
1000
1750
1290
440/460V
hp
kW
100
75
150
110
200
150
250
185
350
260
450
330
500
370
550
410
650
485
800
600
900
670
1150
820
1350
1000
1600
1175
200
1475
575V
hp
kW
150
110
200
150
300
220
350
260
450
330
550
410
650
475
750
550
850
630
1100
800
1200
900
1500
1200
1750
1290
2000
1475
2500
1850
55ºC
55ºC
Table 10.2
– Powers and currents for connection inside the motor delta with six cables according to UL508
(Room Temperature of 55ºC)
(1)
Power valid for room temperature of 40ºC.
(1)
Power valid for room temperature of 40ºC.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]