CHAPTER 3 - INSTALLATION AND CONNECTION
31
First install and partially tighten the mounting bolts, in agreement with
figures 3,1 and 3,4 and table 3.1, then install the Soft- Starter SSW-06
and tighten the mouthing bolts.
Figure 3.5
- Procedures for HMI removal and front cover
opening of the control connections
3.2
ELECTRICAL
INSTALLATION
DANGER!
The Soft-Starter SSW-06 cannot be used as an emergency stop device.
DANGER!
Be sure that the AC input power is disconnected before making any
terminal connections.
ATTENTION!
The information below will be a guide to achieve a proper installation.
Also follow all applicable local standards for electrical installations.
Provide at least a 0.25m (10 in) space between the sensitive equipment
and wiring from the Soft-Starter SSW-06, and the cables between the
Soft-Starter SSW-06 and the motor. Example: PLC, temperature wiring,
thermocouple cables, etc.
Figure 3.6
- Standard power/grounding connections
R/1L1 S/3L2 T/5L3
Circuit-breaker
Line
Fuses
T
S
R
U/2T1
PE
V/4T2 W/6T3