CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
86
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Figure 6.6 a) and b) -
Current Limit by Current Ramp during Starting
P120
(1)
1 to 3
Starting Torque
[ 1=Constant ]
Characteristics
-
P120
Starting Torque Profile
1
Constant (1 setting point)
2
Linear (2 setting points)
3
Quadratic (3 setting points)
It enables choosing which torque limit profile the Soft-Starter SSW-06
will supply to the motor during the start.
Three different types of Torque Limit Profile are available allowing the
start of any type of load: constant or 1 point, linear or 2 points and
quadratic or 3 points.
Figure 6.7 a) to c) -
Available Torque Profile during the start
Table 6.2
- Starting Torque Profile
b)
Tn(%)
P121
Start
P202=1
P102
0
Tn Nominal
Tn(%)
P121
0
t(s)
P102
t(s)
P202=2
Tn Nominal
Start
P122
Tn(%)
P121
0
P102
t(s)
P202=3
Tn Nominal
Start
P122
P123
P124
a)
b)
c)
Start
P102
0
P111
I(A)
Rated Current
t(s)
Disable
Enable
Current Limit
P110
P112
I Limit
Maximum Time