CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
91
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P202
(1)
0 to 4
Type of Control
[ 0=Voltage
Ramp ]
-
P202
0
1
2
3
4
Type of Control
Voltage Ramp
Current Limit
Pump Control
Torque Control
Current Ramp
Table 6.15 -
Types of control
Soft-Starter SSW-06 has five starting control types to better match all
application requirements.
Start by Voltage Ramp
(1)
:
The start by Voltage Ramp is the most used starting method. Its
programming and setting is very easy. The Soft-Starter SSW-06 applies
the voltage to the motor without voltage or current feedback. This method
is used for loads with lower initial torque or quadratic torque.
This type of control can be used as initial operating test.
Start by Current Limit
(2)
:
The maximum current level is maintained during the start and is set
according to the application requirements. Its programming and setting
is very easy.
This method is used for loads with higher initial torque or constant torque.
This type of control is used for matching the start process to the limits of
the power supply capacity.
Start by Current Ramp
(3)
:
The maximum current level is limited during the start process, however
higher or lower current limits can be set during the start beginning.
6.3 CONFIGURATION PARAMETERS - P200 to P299
With the Factory Setting, the password will be P000=5.
To change the Password, see P000.
P200
0 or 1
Password
[ 1 ]
-
P200
0 (inactive)
1 (Active)
Action
This Parameter allows parameter content changing,
independent of P000
Change of Parameter content is only possible, when P000 is
equal to the password value
P201
(2)
0 to 3
Language Selection
[1=English]
-
Table 6.13
- Password
P201
0
1
2
3
Description
Portuguese
English
Espanish
German
Table 6.14
- Language selection