![WEG SSW-06.0085 User Manual Download Page 79](http://html.mh-extra.com/html/weg/ssw-06-0085/ssw-06-0085_user-manual_950611079.webp)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
80
Range
[Factory Setting]
Parameter
Unit
Description / Notes
RL1...RL3 Status
P012=101
DI1...DI6 Status
P012=100100
Indicates on the keypad LCD display the status of the 3 relay outputs
of the control board. Number 1 stands for Active and 0 for Inactive, in
the following order:
RL1, RL2, RL3.
The keypad LED display shows the decimal value that corresponds to
the status of the 3 digital outputs, where the status of each bit is
considered one bit in the specified sequence:
Inactive=0
Active=1
RL1 status is the most significant bit.
The 5 least significant bits are always ‘0’.
Example:
RL1=Active; RL2=Inactive; RL3=Active
This is equivalent to the binary sequence:
10100000
Which corresponds to the decimal number 160.
The least significant bits are not displayed.
The Keypad displays will be:
P013
LCD=1,0
Digital Outputs
LED=0 to 255
RL1 to RL3 Status
[ - ]
-
Indicates on the keypad LCD display the status of the 6 digital inputs
of the control board (DI1 to DI6). Number 1 stands for Active and Number
0 for Inactive, in the following order: DI1, DI2,...,DI5, DI6.
The LED Display shows a decimal value corresponding to the status
of the 6 digital inputs, where the status of each bit is considered one
bit in the specified sequence:
Inactive=0
Active=1
DI1 status is the most significant bit.
Example:
Dl1 = Active (+24V);
Dl4 = Active (+24V);
Dl2 = Inactive (0V);
Dl5 = Inactive (0V);
Dl3 = Inactive (0V);
Dl6 = Inactive (0V).
It is equivalent to the bit sequence:
10010000
Which corresponds to the decimal number 144.
The least significant bits are not displayed.
The keypad displays will be as follows:
P012
LCD=1,0
Digital Input Status
LED=0 to 255
DI1 to DI6
[ - ]
-