CHAPTER 5 - START-UP
66
5.2 INITIAL POWER-UP
(required parameter settings)
After the Soft-Starter SSW-06 has been checked, AC power can be
applied:
1) Check the supply voltage:
Measure the line voltage and check if it is within the specified range
(Rated Voltage - 15% to + 10% ).
2) Power-up the Electronics Supply:
NOTE!
Always energize the electronics supply before energizing the power
and execute all adjustments/settings described in this item.
3) Check if the power-up has been successful
When the Soft-Starter SSW-06 is powered up for the first time or
when the factory default parameter values are loaded (P204 = 5), a
start-up routine is run.
This routine requests the user to program some basic parameters
to ensure proper Soft-Starter SSW-06 and operation and motor
operation.This routine sequence changes according to the selected
type of control. For more details about the control type to be selected,
refer to Parameter P202 in Chapter 6.
The parameterization sequence for each control type is show in
figure 5.1.
ATTENTION!
For correct programming of the protection parameters, please consider
the catalog data and the motor nameplate data of the used motor.
To protect the motor against overloads during the start process and at
during operation, program the thermal class of the motor. For more
details about programming of the Thermal Class, see description of
Parameter P640 in Chapter 6.
In this parameter setting sequence only the main parameters for learning
about the Soft-Starter SSW-06 operation are shown. Please program
all necessary parameters for correct operation of the Soft-Starter and
motor protection, before operating it at rated operation conditions.
4) Close the input circuit-braker.