CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
108
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Figura 6.19
- Reverse Braking
Start
U(V)
100%Un
Enable
Disable
Start
P502
t(s)
P501
FWD/REV-K2 Closed
FWD/REV-K1 Closed
1s
0
NOTES!
1. The contactors must be the same model and withstand the
motor starting current. For security use auxiliary contact to
avoid the contactors to close at the same time. For security,
use an auxiliary contact to avoid contactors closing at the
same time.
2. Use a digital input set to the “Braking Off” option to avoid
starting the motor again in the wrong direction.
3. Por segurança uma entrada digital programada como “Sem
frenagem”, para possibilitar a utilização de um sensor de
parada no motor que desabilite a frenagem imediatamente,
evitando que o motor gire em sentido contrário.
4. The Soft-Starter SSW-06 protects the motor while the
Reverse Braking AC level is applied.
5. See the parameters: P266, P267, P268, P277, P278, P500,
P501, P502, and P503 and see the recommended setup
set-up at 3.3 and 3.3.9.
“Optimal Braking”
This is an efficient method to stop loads.
The direct current is only applied when it will go to produce braking
effect. when it produces a braking effect.
No contactor needed.
It’s compatible with the inside delta motor connection.
Figura 6.20
- Optimal Braking
Start
U(V)
100%Un
Enable
Disable
P501
t(s)
P502
1s
0