CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
107
Range
[Factory Setting]
Parameter
Unit
Description / Notes
6.6 SPECIAL FUNCTION PARAMETERS - P500 to P599
P500
Action
0
Inactive
1
Reverse Braking
2
Optimal Braking
3
DC-Braking
Table 6.32
- Braking Methods selection
There are three braking methods implemented in the Soft-Starter
SSW-06. These braking methods should be used only when fast
stop is necessary. stops are necessary.
Figure 6.18
- Braking Torque
“Reverse Braking”
This is an efficient method to stop very high inertia loads.
The motor will stop via AC level voltage in reverse direction until near
20% of the nominal speed when a Optimal Braking is applied to stop
the motor.
The motor will stop via AC level voltage in reverse direction until close
to 20% of the rated speed, when Optimal Braking is applied to stop
the motor.
The Reverse Braking AC level and Optimal Braking are set in P502.
Two contactors are needed.
It is compatible with the Soft-Starter SSW-06 inside delta motor
connection, except for two and eight pole motors.
P501
Stopped
Disable
Nominal
Speed
Braking
Torque
DC-Braking
Reverse Braking
Optimal Braking
P500
(1)
Braking Methods
0 to 3
[ 0=Inactive ]
-