V04.00 | 2021/05
225
14.2
Techincal data – TBEN-S1-8DIP
The device has eight digital inputs for 3-wire PNP sensors.
Technical data
Power supply
Operating current (from V1)
< 150 mA
Sensor/actuator supply VAUX1
Supply connector C0…C7 from V1
short-circuit proof, 0.5 A per group C0…C3,
C4…C7
Potential isolation
From V1 and V2 voltage group,
voltages up to 500 VDC
Digital inputs
Number of channels
8
Connection technology
M8, 3-pin
Input type
EN 61131-2 type 3, PNP
Type of input diagnostics
Group diagnostics
Signal voltage low level
< 5 V
Signal voltage high level
> 11 V
Signal current low level
< 1.5 mA
Signal current high level
> 2 mA
Input resistance low level
Min. 3.33 kΩ
Input resistance high level
Max. 5.5 kΩ
Input delay
0.2 ms/3 ms
Input frequency
400 Hz
Potential isolation
Galvanic isolation to P1/P2,
voltage proof up to 500 VDC
General information
MTTF
319 years acc. to SN 29500 (Ed. 99) 20 °C