V04.00 | 2021/05
173
9.2
Evaluating diagnostic data
The diagnostics of the TBEN-S devices are mapped into the process data [
9.2.1
PROFINET diagnostics
TBEN-S1-8DIP – diagnostic data mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
-
-
-
-
-
-
VERR V1
ch4-7
VERR V1
ch0-3
n + 1
-
-
-
-
-
-
-
-
PROFINET error codes
Station diagnostics (slot 0)
PROFINET diagnostics
Diagnostics
Error code
Channel
Undervoltage
V1
0x0002
0
V2
0x0002
1
I/O diagnostics (slot 1)
PROFINET diagnostics
Diagnostics
Connector/pin
Error code
Channel
Overcurrent supply group
Overcurrent supply VAUX1 at channel 0…3
VERR V1 K 0-3
C0
0x0130
0
C1
C2
C3
Overcurrent supply group
Overcurrent supply VAUX1 at channel 4…7
VERR V1 K 4-7
C4
0x0131
0
C5
C6
C7