Operating
Measurement value representation of analog modules
198
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
-20…20 mA
Diagnostics
Decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 10
-4
) mA
> 22.00 mA
"Overload/Overcurrent" ON
> 22000
> 55F0
< 21.80 mA
"Overload/Overcurrent" OFF
> 21800
> 5528
> 21.00 mA
"Upper limit value exceeded” ON
> 21000
> 5208
< 20.50 mA
"Upper limit value exceeded" OFF
> 20500
> 5014
22.00 mA
Nominal range
22000
55F0
21.00 mA
21000
5208
10.00 mA
10000
2710
4.00 mA
4000
0FA0
0.00 mA
0
0000
-10.00 mA
-10000
D8F0
-21.00 mA
-21000
ADF8
-22.00 mA
-22000
AA10
> -20.50 mA
"Lower limit value underrun" OFF
> -20500
> AFEC
< -21.00 mA
"Lower limit value underrun" ON
> -21000
< ADF8
> -21.80 mA
"Underflow" OFF
> -21800
> AAD8
< -22.00 mA
"Underflow" ON
> -22000
< AA10